How to Evaluate Surge Protection Devices: Key Specifications and What They Really Mean
How do you evaluate surge protection devices? Datasheets can be confusing when you’re purchasing a surge protection device (SPD). What information reflects real performance, and what is just marketing? These are the criteria you should look for on any SPD datasheet. If the information isn’t provided, you should ask yourself why—because the following topics are considered industry standard when it comes to surge protection.
Nominal Discharge Current
Nominal discharge current is the baseline test for SPDs. It measures whether the device can withstand repeated surges without damage or degradation. The standard procedure applies 15 surges within a 3-hour period.
When reviewing a datasheet, pay close attention to the value at which the SPD was tested. For main service panels or any high-exposure area, you should select a device with the highest testing level of 20 kA (In). This is the most rigorous test commonly performed and is strongly recommended. Other common levels you may see are 10 kA, 5 kA, and 3 kA.
Modes of Protection
SPDs can be designed with full (discrete) protection modes or reduced modes. Reduced-mode SPDs typically omit certain pathways, often lacking line-to-ground (L-G) protection. While this design can lower manufacturing costs, it often results in higher let-through voltages, making the SPD less effective.
Always confirm whether the device provides full protection across all modes—especially L-G protection.
Peak Surge Current Rating: Per Mode vs. Per Phase
The per mode peak surge current rating is generally more important than the per phase rating, because it shows the maximum surge current a specific protection pathway (e.g., line-to-neutral or line-to-ground) can handle without failure.
Per Mode Rating
This rating indicates the maximum surge current the SPD can handle in each specific path:
- Line-to-neutral (L-N)
- Line-to-ground (L-G)
- Neutral-to-ground (N-G)
For example, a surge traveling from a live wire to ground stresses the L-G pathway. The per mode rating tells you whether the device can safely absorb that surge.
Per Phase Rating
This is the total surge current capacity of the device, calculated by summing the ratings across all modes. While it provides a broad measure of surge handling capability, it does not guarantee protection in any single pathway.
Why Per Mode Matters More
If a surge exceeds the per mode rating of a specific path (for example, L-G), the SPD may fail—even if the overall per phase rating is higher. That’s why per mode ratings give a clearer, more reliable picture of protection.
Example:
If an SPD has:
- L-N per mode rating: 100 kA
- L-G per mode rating: 50 kA
- Per phase rating: 150 kA
A 60 kA surge traveling L-G will exceed the 50 kA per mode rating and potentially destroy the SPD, despite the higher total per phase rating.
In short, per mode ratings are a more accurate indicator of performance under real-world conditions.
VPR Ratings (Voltage Protection Rating)
SPDs listed under UL 1449 5th Edition must include a VPR rating. VPR indicates how much surge voltage remains after the SPD clamps the surge.
- A lower VPR means better protection for downstream equipment.
- A higher VPR allows more voltage through, which can damage sensitive loads.
Always prefer SPDs with the lowest VPR practical for your application.
SCCR – Short-Circuit Current Rating
The Short-Circuit Current Rating (SCCR) indicates the maximum available fault current an SPD can safely withstand and disconnect from during a short-circuit event.
It is important to note that:
- SCCR is not the same as AIC (Ampere Interrupting Capacity).
- AIC refers to the maximum fault current that a device can safely interrupt without damage. (like a fuse or circuit breaker)
- SCCR refers to maximum fault current that the complete piece of equipment (like panel or SPD can safely withstand without causing a hazard.
- SCCR does not describe the SPDs ability to disconnect from the circuit. Instead, it defines the maximum short circuit current the SPD (or any equipment) can withstand without causing fire, explosion or other hazard.
- The disconnection function is related to the internal overcurrent protection or fuse coordination within the SPD, not the SCCR itself
- The actual interrupted current is usually significantly less than the available fault current.
Make sure the SCCR is appropriate for the power system where you’ll install the SPD.
A word on warranties
An important component when evaluating SPDs is the warranty coverage provided. Not all warranties are created equally and it is worth reading the fine print. For example, a “lifetime warranty” may sound great, but if it only covers workmanship and product defects, that won’t be of much help if the SPD you have selected fails in the course of duty. This article takes a deeper dive into Surge Protection Warranties and What They Actually Cover.
Conclusion
By carefully reviewing these specifications—nominal discharge ratings, modes of protection, per mode ratings, VPR, response time, and SCCR—you can make an informed decision and evaluate surge protection devices that provide reliable, long-lasting surge protection. If any of this information is missing from the datasheet, be cautious and ask the manufacturer for clarification. Always read the warranty provided by the manufacturer to understand what it covers.