What are internal oscillatory transients and how do they impact facilities? Modern industrial, institutional, and municipal facilities depend heavily on sensitive electronic infrastructure. PLCs, VFDs, BAS systems, instrumentation, communication networks, and digital control systems now sit at the centre of everyday operations. As facilities become more automated, the reliability of these systems becomes increasingly important.

Most electrical protection strategies focus on external surge events such as lightning strikes or utility switching disturbances. While these are legitimate concerns, they are not the primary source of damaging electrical transients inside most facilities.

According to IEEE C62.41.2, the majority of transient activity affecting sensitive electronics originates internally. These disturbances are commonly represented by what the IEEE defines as an oscillatory ringwave transient.

Understanding the difference between impulse surges and ringwave transients is critical because the protection technologies commonly installed in switchgear are often optimized for one type of event while offering limited effectiveness against the other.

What Is a Ringwave Transient?

IEEE C62.41.2 defines a ringwave as a decaying oscillatory waveform with a nominal frequency of approximately 100 kHz. These events are most common in downstream distribution systems and branch circuits, categorized by IEEE as Category A and Category B environments.

Ringwave transients are typically generated by normal facility operations, including:

  • VFD and motor switching
  • Capacitor bank switching
  • Relay and contactor operation
  • Sudden load changes
  • Distributed power system interactions

Unlike lightning-induced impulse surges, ringwave events generally occur at lower peak voltages but happen far more frequently. Rather than delivering a single high-energy spike, they introduce oscillatory energy into the electrical system over a short duration.

This distinction is important because many surge protection devices are designed primarily to respond to voltage magnitude, not waveform behaviour or frequency content.

For more information, read our previous article: Protecting Against A1 and A3 Ring Waves: Why Surge Protection Matters

Understanding the Frequency Gap

One of the most misunderstood aspects of transient protection is the frequency range involved.

Power systems operate at 50 or 60 Hz. VFD switching frequencies commonly range from several kilohertz into the tens of kilohertz. Standard conducted EMI is generally considered to begin around 150 kHz and extend upward into the megahertz range.

Ringwave transients occupy a region around 100 kHz, placing them between traditional surge protection and conventional EMI filtering.

This creates a significant protection gap.

The issue is not that EMI/RFI filters are defective. The issue is that they are designed for a different frequency range than the disturbance they are being asked to mitigate.

A useful analogy is tuning a radio to FM and expecting to receive AM signals. The radio may function perfectly, but it is operating in the wrong frequency band for the application.

Why MOV-Based SPDs Often Miss Ringwave Events

Most surge protective devices installed in switchgear today rely primarily on Metal Oxide Varistors, commonly known as MOVs.

MOVs are extremely effective at managing high-energy impulse surges such as lightning events or utility switching disturbances. They operate by remaining in a high-impedance state during normal conditions and rapidly transitioning into conduction when voltage exceeds a defined threshold.

Once that threshold is exceeded, the MOV diverts surge energy to ground.

This approach works well for large impulse events. However, ringwave transients behave differently.

Many oscillatory transients:

  • Do not exceed the MOV clamping threshold
  • Deliver energy over time rather than in a single impulse
  • Produce oscillatory behaviour rather than a sharp voltage spike

As a result, the MOV may never fully transition into conduction. The transient energy simply passes downstream into sensitive electronic equipment.

In practical applications, this can lead to repetitive low-level stress on power supplies, instability in control systems, intermittent PLC faults, nuisance shutdowns, and premature failure of electronic components.

These failures are often difficult to diagnose because the damaging events are brief, repetitive, and rarely catastrophic in a single occurrence.

Why Standard EMI/RFI Filters Are Also Limited

Many switchgear manufacturers state that their SPDs include filtering. Technically, this is correct. However, the type of filtering matters.

Most integrated EMI/RFI filters are designed specifically to meet conducted emissions standards such as CISPR or FCC requirements. Their primary purpose is to attenuate high-frequency electrical noise, typically in the range of 150 kHz to 30 MHz.

To achieve this, they use relatively small inductors and low-value capacitors.

At frequencies around 100 kHz, these components often do not present sufficient impedance to meaningfully attenuate ringwave energy.

The inductive reactance is too low, while the capacitive reactance remains too high. The result is minimal damping of oscillatory transients in the frequency range where ringwave disturbances exist.

Again, the issue is not that the filters are malfunctioning. They are simply optimized for megahertz-range noise suppression rather than kilohertz-range oscillatory transient mitigation.

The Resulting Protection Gap

This leaves facilities with a common but poorly understood problem.

MOV-based SPDs effectively address high-energy overvoltage events.

EMI/RFI filters effectively address high-frequency conducted noise.

Neither technology is particularly effective against low-amplitude oscillatory transients centered around 100 kHz.

As a result, sensitive electronic equipment often absorbs the residual energy directly.

This explains why facilities can experience repeated electronic failures even when they have properly installed surge protection devices.

Effective Approaches to Ringwave Mitigation

Mitigating oscillatory transients requires a different design philosophy than conventional surge suppression.

The key principle is simple: transient mitigation depends on impedance at the frequency of the disturbance.

If a protection device does not present meaningful impedance at approximately 100 kHz, it cannot effectively attenuate ringwave energy regardless of its surge current rating.

Series Impedance and Inductive Protection

One of the most effective methods for addressing ringwave transients is the introduction of series impedance through inductive elements.

Unlike MOVs, impedance-based protection does not rely on voltage thresholds. Instead, it opposes rapid changes in current and dissipates transient energy over time.

At ringwave frequencies, inductive reactance becomes significant enough to naturally damp oscillatory energy.

This is why properly designed low-frequency power line filters are physically larger than standard EMI filters. They require larger inductors and higher capacitance values in order to function effectively in the kilohertz frequency range.

Hybrid Protection Systems

The most robust protection systems typically combine multiple technologies.

A properly engineered hybrid design may include:

  • MOVs for high-energy impulse protection
  • Series impedance for oscillatory transient attenuation
  • Damping networks for waveform control

In these systems, the MOV addresses extreme surge events while the impedance network mitigates internally generated ringwave disturbances.

This layered approach provides broader protection coverage across multiple transient types and frequency ranges.

Ferrite Components

Ferrite materials can also provide supplementary attenuation, particularly at higher frequencies above 1 MHz. Some MnZn ferrite materials extend lower into the frequency spectrum, but ferrites alone are generally insufficient as a primary ringwave mitigation strategy.

Reliability, Maintenance, and SPD Location

Beyond electrical performance, SPD placement has significant implications for long-term maintenance and operational risk.

Internally mounted SPDs may appear convenient, but they introduce challenges in critical facilities. If a sufficiently large surge event causes an internal SPD to fail, replacement may require powering down the switchgear.

For hospitals, long-term care facilities, multi-residential buildings, data infrastructure, or municipal operations, this downtime can become extremely disruptive and expensive.

Many facility operators avoid replacing failed internal SPDs altogether because of the operational complexity associated with shutdowns and restoration procedures.

Externally mounted SPDs supplied through dedicated breakers offer a more maintainable solution. They allow rapid replacement with minimal coordination and reduced operational disruption while lowering the risk of damage occurring inside the switchgear enclosure itself.

This approach aligns more closely with long-term reliability objectives for critical infrastructure.

Final Thoughts on Internal Oscillatory Transients

Internal oscillatory transients remain one of the most under-addressed causes of electronic equipment failure in modern facilities.

MOV-based SPDs are essential for managing high-energy impulse surges, but they are not designed to address all transient types. Likewise, standard EMI/RFI filters are optimized for megahertz-range noise suppression rather than the kilohertz-range oscillatory disturbances defined by IEEE ringwave standards.

Effective transient mitigation requires protection technologies that present meaningful impedance at the frequency where the disturbance actually exists.

In practical terms, if a protection device does not address the approximately 100 kHz frequency range associated with ringwave transients, protection remains incomplete regardless of surge current ratings or marketing claims.